PDJ Type Low Voltge Automation System


pdj型低压机组自动化系统_副本


Scope of application

  • It is applicable to the computer monitoring, automatic control, protection, measurement,signaling, telecontrol and other automation functions for 400V Low Voltage turbine generator.

Main technical parameters

  • It is suitable for the unit with generator rated voltage of 400V and installed capacity ranges from 100kW to 800kW; The RS485 or Ethernet interface is provided to communication with upper computer and remotedispatching center;
  • Acquisition of 16-loop DIs;
  • 128sequence of event (SOE) record;
  • 60 cycles fault record before andafter failure;
  • The sync-check, no-voltage check synchronization function
  • Sync. phase difference: 1.0°~20.0°;
  • Sync. voltage difference: 1.0V~20.0V;
  • sync. frequency difference: 0.02Hz~0.50Hz;
  • No-voltage setting 5.0V~50.0V;
  • Valid time for closing operation: 0.1s~20.0s;
  • The excitation function configurable
  • Excitation voltage: 0~100V;
  • Excitation current: 0~10A;
  • Maximumexcitation current: 20A
  • It is suitable for ACexciter and low voltage brushless excitation system.
  • Overall dimension:
  • GGD cabinet  1200×800×2260 (W*D*H)
  • Operating environment: -10℃~+55℃, relative humidity ≤ 90%, elevation below 3000m.

  • Click here to get operation manual